|     | Caledonian FIRETOX Cables
 
 CABLE CONSTRUCTION
 FIRETOX cables are constructed in the following typical design:
 1. Solid/stranded annealed copper conductor
 2. XLPE/LSZH as insulation
 4. LSZH/flame retardant LSFROH as sheath
 FIRETOX cables are offered in either single core, multicore or multi-pair constructions.
 The insulation material can be thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.
 
 INTERNATIONAL STANDARD
 The FIRETOX cables manufactured by Caledonian comply with either one or combination of the following standards.
 IEC 60332-1
 IEC 60332-3C
 IEC 61034-1/2
 IEC 60754-1
   |  |  | PRODUCTSFire Retardant PVC Sheathed Cables (FIRETOX)  Flame Retardant Instrumentation Cables
 Flame Retardant Individual and Overall Screened, Armoured Instrumentation Cables
        (Multipair)
 APPLICATION
 The armoured LSZH versions (Part 1 Type 2) cables are generally used when the risk of mechanical
 damage is increased. The galvanized steel wire armour provides excellent protection. Generally
 used within industrial process manufacturing plants for communication, data and voice transmission
 signals and services, Also used for the interconnection of electrical equipment and instruments, the
 LSZH sheath can reduce toxic smoke and fume emission.
 STANDARDS
 Basic design adapted to BS 5308 Part 1 Type 2
 VOLTAGE RATING
 300/500V
 CABLE CONSTRUCTION
 Conductor: Annealed or tinned copper, sizes: 0.5mm² and 0.75mm² mulitistranded(Class 5), 0.5
 mm², 1.0 mm² solid(Class 1), 1.5mm² or 2.5mm², multistranded(Class 2) to BS6360
 Insulation: XLPE (Cross Linked Polyethylene), or PE (optional)
 Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
 Individual Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in
 contact with tinned copper drain wire, 0.5mm²
 Binder tape: PETP transparent tape
 Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in
 contact with tinned copper drain wire, 0.5mm²
 Inner Sheath: LSOH(Low Smoke Zero Halogen) sheath
 Amouring: Galvanized steel wire armour
 Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting
 LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon
 resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
 COLOUR CODE
 Insulation Colour: See technical information
 Outer Sheath: Black or blue
 Physical AND THERMAL PROPERTIES
 Maximum Operating temperature: -20˚C - + 90˚C( fixed installation)
 0˚C - +50˚C(during operation)
 Minimum bending radius: 6 x Overall Diameter
 
  
 