Caledonian FIRETOX Cables


CABLE CONSTRUCTION
FIRETOX cables are constructed in the following typical design:
  1. Solid/stranded annealed copper conductor
   2. XLPE/LSZH as insulation
  4. LSZH/flame retardant LSFROH as sheath
FIRETOX cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.

INTERNATIONAL STANDARD
The FIRETOX cables manufactured by Caledonian comply with either one or combination of the following standards.
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1

 

 

PRODUCTS

Fire Retardant PVC Sheathed Cables (FIRETOX)
Flame Retardant Instrumentation Cables
Flame Retardant Overall Screened, Armoured Instrumentation Cables (Multipair)
APPLICATION

The armoured LSZH versions (Part 1 Type 2) cables are generally used when the risk of mechanical
damage is increased. The galvanized steel wire armour provides excellent protection. Generally
used within industrial process manufacturing plants for communication, data and voice transmission
signals and services, Also used for the interconnection of electrical equipment and instruments, the
LSZH sheath can reduce toxic smoke and fume emission.
STANDARDS
Basic design adapted to BS 5308 Part 1 Type 2
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor: Annealed or tinned copper, sizes: 0.5mm² and 0.75mm² mulitistranded(Class 5), 0.5
mm², 1.0 mm² solid(Class 1), 1.5mm² or 2.5mm², multistranded(Class 2) to BS6360
Insulation: XLPE (Cross Linked Polyethylene), or PE (optional)
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Binder tape: PETP transparent tape
Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in
contact with tinned copper drain wire, 0.5mm²
Inner Sheath: LSOH(Low Smoke Zero Halogen) sheath
Amouring: Galvanized steel wire armour
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting
LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon
resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE
Insulation Colour: See technical information
Outer sheath: Black or blue
Physical AND THERMAL PROPERTIES
Maximum Operating temperature: -20˚C - + 90˚C( fixed installation)
0˚C -+50˚C(during operation)
Minimum bending radius: 6 x Overall Diameter