Caledonian FIRETOX Cables


CABLE CONSTRUCTION
FIRETOX cables are constructed in the following typical design:
  1. Solid/stranded annealed copper conductor
   2. XLPE/LSZH as insulation
  4. LSZH/flame retardant LSFROH as sheath
FIRETOX cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.

INTERNATIONAL STANDARD
The FIRETOX cables manufactured by Caledonian comply with either one or combination of the following standards.
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1

 

 

PRODUCTS

Fire Retardant PVC Sheathed Cables (FIRETOX)
Flame Retardant Instrumentation Cables
Flame Retardant Overall Screened Instrumentation Cables (Multicore)
APPLICATION

The LSZH versions (Part 1 Type 1&2) cables are generally use for indoor installation and suitable
for wet and damp areas. Generally used within industrial process manufacturing plants for
communication, data and voice transmission signals and services, Also used for the interconnection
of electrical equipment and instruments, the LSZH sheath can reduce toxic smoke and fume
emission.
STANDARDS
Basic design adapted to BS 5308 Part1 Type1 & 2
VOLTAGE RATING

300/500V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 and 5 .
Insulation: Extruded cross-linked XLPE compound.
Overall Screen: Aluminium/polyester tape with 0.5mm2 screen (7/0.3mm) tinned copper drain wire.
Inner Sheath(optional): LSZH compound
Armouring(optional): Galvanised steel wire
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting
LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon
resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE
Insulation Colour: See technical information
Outer sheath: Black or blue
Physical AND THERMAL PROPERTIES

Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5s max.
Minimum bending radius: 8 x Overall Diameter (unarmoured cable)
10 x Overall Diameter (armoured cable)
Flame Retardant Overall Screened Instrumentation Cables (Multicore)



Download details in PDF

Download details in Word