Caledonian FIRETOX Cables


CABLE CONSTRUCTION
FIRETOX cables are constructed in the following typical design:
  1. Solid/stranded annealed copper conductor
   2. XLPE/LSZH as insulation
  4. LSZH/flame retardant LSFROH as sheath
FIRETOX cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.

INTERNATIONAL STANDARD
The FIRETOX cables manufactured by Caledonian comply with either one or combination of the following standards.
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1

 

 

PRODUCTS

Fire Retardant PVC Sheathed Cables (FIRETOX)
Flame Retardant Power & Control Cables
600/1000V XLPE Insulated, LSZH Sheathed, Double steel tape Armoured Power Cables (3 Cores)
APPLICATION
The cables are mainly used in power stations, mass transit underground passenger systems,
airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS
Basic design adapted to IEC 60502-1
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, normal stranded or compact stranded according to IEC(EN)
60228 class 2.

Insulation: Extruded cross-linked XLPE compound.
Filler, binder and inner covering: PP, PET, LSZH
Armouring: Double steel tape
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting
LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon
resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5s max.
Minimum bending radius: 10x Overall Diameter