CABLE CONSTRUCTION
fireflix cables are constructed in the following typical design:
  1. Solid/stranded annealed copper conductor
   2. Glass mica tape/silicone rubber as flame barrier
  3. XLPE/silicone rubber as insulation
  4. LSZH/Flame retardant RPVC as sheath
fireflix cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be elastomeric (EPR, SR), thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.

INTERNATIONAL STANDARD
The fireflix cables manufactured by Caledonian comply with either one or combination of the following standards.
BS 6387
IEC 60331
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1

 

 

PRODUCTS

Fire Resistant Fire Alarm Cables
300/500V SR Insulated & LSZH Sheathed Fire Alarm Cables
FFX200P 05SOZ1-U (PH30) (CU/SR/OSCR/LSZH 300/500V Class 1)
FFX200P 05SOZ1-R (PH30) (CU/SR/OSCR/LSZH 300/500V Class 2)
APPLICATION
The cables are designed, manufactured and tested as data transmission cables for emergency services. These are primarily intended for for indoor instrumentation and control cabling, electrically noisy environments and fire alarm systems in office buildings when high frequency signal transmission has to be assured in the event of a fire.
STANDARDS
Basic design to BS 7629-1
Fire Performance

Circuit Integrity

IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);
BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)

Circuit Integrity with mechanical shock

EN 50200(PH30); CEI 20-36/4-0

Circuit Integrity with mechanical shock & water spray

EN 50200 annex E

System circuit integrity

DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;
VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;
CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;
CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.
CABLE CONSTRUCTION
Conductors:
Plain annealed copper wire, solid according to IEC(EN) 60228 class 1, stranded according to IEC(EN) 60228 class 2.
Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
Cabling Elements: Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two-pair cable had four cores laid in quad formation.
Cabling: Pairs are cabled together in concentric layers with suitable non-hygroscopic fillers.
Overall screen: Aluminum/polyester tape with tinned copper drain wire.
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
Colour code
Insulation Colour:
Cables up to 6 pairs black-red / black-blue / red-blue / yellow-black /yellow-red / yellow-blue
Cables above 6 pairs all pairs black-red numbered on the wrapping tape.
Sheath Colour: Colour red (other colours on request).
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 7.5 x Overall Diameter
Fire Resistant Fire Alarm Cables

Download details in PDF

Download details in Word