          Caledonian fireflix Cables 
           
          CABLE CONSTRUCTION 
  fireflix cables are constructed in the following typical design: 
  1. Solid/stranded annealed copper conductor 
   2. Glass mica tape/silicone rubber as flame barrier 
  3. XLPE/silicone rubber as insulation 
  4. LSZH/Flame retardant RPVC as sheath 
  fireflix cables are offered in either single core, multicore or multi-pair constructions. 
  The insulation material can be elastomeric (EPR, SR), thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.  
       INTERNATIONAL STANDARD  
  The fireflix cables manufactured by Caledonian comply with either one or combination of the following standards. 
  BS 6387 
  IEC 60331 
  IEC 60332-1 
  IEC 60332-3C 
  IEC 61034-1/2 
  IEC 60754-1         
        
       | 
     | 
      | 
    
      PRODUCTS
      Fire Resistant Instrumention Cables 
        RE-2X(St)H...CI. FE 180 PH30 ( CU/MGT+XLPE/OSCR/LSZH 300/500V Class 2 )  
        RE-2G(St)H...CI. FE 180 PH30 ( CU/SR/OSCR/LSZH 300/500V Class 2 ) 
  RE-2X(St)HSWAH...CI. FE 180 PH30 ( CU/MGT+XLPE/OSCR/LSZH/SWA/LSZH 300/500V Class 2 ) 
  RE-2G(St)HSWAH...CI. FE 180 PH30 ( CU/SR/OSCR/LSZH/SWA/LSZH 300/500V Class 2 ) 
        APPLICATION 
        The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire. 
        STANDARDS 
        Basic design to BS 5308/BS 7629-1  
        FIRE PERFORMANCE 
      
        
          
            Circuit Integrity  | 
            IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);  
              BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) 
                 | 
           
          
            Circuit Integrity with mechanical shock  | 
            EN 50200(PH30); CEI 20-36/4-0  | 
           
          
            Circuit Integrity with mechanical shock & water spray  | 
            EN 50200 annex E  | 
           
          
            System circuit integrity  | 
            DIN 4102-12, E30 depending on lay system  | 
           
          
            Flame Retardance (Single Vertical Wire Test)  | 
            EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;  
              VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);  
              CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* 
                 | 
           
          
            Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)  | 
            EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4  | 
           
          
            Halogen Free  | 
            IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;  
              CEI 20-37/2-1 ; BS 6425-1* 
                 | 
           
          
            No Corrosive Gas Emission  | 
            IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;  
              CEI 20-37/2-2 ; BS 6425-2* 
                 | 
           
          
            Minimum Smoke Emission  | 
            IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;  
              CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* 
                 | 
           
          
            No Toxic gases  | 
            NES 02-713; NF C 20-454  | 
           
        
       
      Note: Asterisk * denotes superseded standard. 
        CABLE CONSTRUCTION 
        Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2. 
        Insulation: Mica glass tape covered by extruded cross-linked XLPE compound or fire resistant silicone rubber compound type EI2 as per BS 7655-1.1. 
        Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers. 
        Overall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire. 
        Inner Sheath(optional):Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1  
        rmouring(optional): Galvanized steel wire armour 
        Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1(Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.) 
        VOLTAGE RATING  
        300/500 V 
        COLOUR CODE 
        Insulation Colour: White with black numberings. 
        Sheath Colour: Orange (other colours on request). 
        TYPE CODE 
        RE- Instrumentation cable H Halogen free & zero halogen  
        2X XLPE 2G Silicon Rubber  
        (St) Static shield of aluminium tape SWA Steel Wire Armoured 
        FE180 Insulation integrity (950°C 180 minutes) CI Circuit integrity 
        PH 90 Fire Test for 90 mins at 830°C  
        Physical AND THERMAL PROPERTIES 
        Temperature range during operation (fixed state): -30°C – +90°C 
        Temperature range during installation (mobile state): -20°C – +50°C 
        Minimum bending radius: 6 x Overall Diameter (unarmoured cables with silicone rubber insulation) 
        8 x Overall Diameter (unarmoured cables with XLPE insulation) 
        10 x Overall Diameter (armoured cables) 
        Electrical PROPERTIES 
      
        
          
            Dielectric test:  | 
            2000 V r.m.s. x 5’ (core/core)  | 
           
          
            Insulation Resistance  | 
            XLPE: ≥1000 MΩ x km (at 20°C) 
                SR: ≥300 MΩ x km (at 20°C) 
              | 
           
          
            Short circuit Temperature   | 
            XLPE: 250°C 
                SR: 350°C  | 
           
        
       
                
        
           
            
          Download details in PDF  