Caledonian fireflix Cables


CABLE CONSTRUCTION
fireflix cables are constructed in the following typical design:
  1. Solid/stranded annealed copper conductor
   2. Glass mica tape/silicone rubber as flame barrier
  3. XLPE/silicone rubber as insulation
  4. LSZH/Flame retardant RPVC as sheath
fireflix cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be elastomeric (EPR, SR), thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.

INTERNATIONAL STANDARD
The fireflix cables manufactured by Caledonian comply with either one or combination of the following standards.
BS 6387
IEC 60331
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1

 

 

 

PRODUCTS

Fire Resistant Coaxial Cables
Fire resistant RG59 B/U Coaxial cables
RG59 B/U FR
APPLICATION
The cables are designed for CCTV, security, smoke detection and evacuation monitoring applications, where continued functionality is required during a fire situation. Due to the zero halogen low smoke construction, this cable is ideal for use in public, commercial and industrial environments.
Standards
Basic design to MIL-C-17 
FIRE PERFORMANCE

Circuit Integrity

IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180);
CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);
NF C32-070-2.3(CR1)

System circuit integrity

DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;
CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;
CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.
CABLE CONSTRUCTION
Conductors: Copper clad steel, solid according to IEC(EN) 60228 class 1.
Insulation: PE wrapped with fire resistant silicone rubber compound type EI2 as per BS 7655-1.1 or fluoropolymer(FEP) compound.
Binder: Glass tape
Overall Screen: Plain copper wire braid
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1(Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C - +70°C
Temperature range during installation (mobile state): -5ºC - +60ºC
Minimum bending radius: 8 x Overall Diameter
Electrical Properties

Impedance

75±5Ω

Capacitance

67 nF/km

Velocity ratio(%)

66

Insulation resistance

>2000 Mohm.Km

Shield coverage

95%

DC resistance

Inner conductor

158 Ω/km

Outer conductor

9.0 Ω/km

Attenuation

Frequency(MHz)

Attenuation (dB/100 m)

Attenuation (dB/100ft)

50

7.4

2.26

100

10.7

3.26

200

15.7

4.79

400

22.7

6.92

500

25.7

7.84

600

28.7

8.75

860

34.8

10.61

1000

38.0

11.59

Return Loss

Frequency(MHz)

Return Loss (dB)

30-300 MHz

>31dB

300-600 MHz

>28dB

600-900 MHz

>24dB


Fire resistant RG59 B/U Coaxial cables

Download details in PDF

Download details in Word

 

Caledonian Cables |FAQ |© 2020