Caledonian fireflix Cables
CABLE CONSTRUCTION
fireflix cables are constructed in the following typical design:
1. Solid/stranded annealed copper conductor
2. Glass mica tape/silicone rubber as flame barrier
3. XLPE/silicone rubber as insulation
4. LSZH/Flame retardant RPVC as sheath
fireflix cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be elastomeric (EPR, SR), thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.
INTERNATIONAL STANDARD
The fireflix cables manufactured by Caledonian comply with either one or combination of the following standards.
BS 6387
IEC 60331
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1
|
|
|
PRODUCTS
Fire Resistant Optic Fiber Cables
Fire Resistant Tight Buffered Distribution Fiber Optic cables
MTA-B-C-D-H-FR
APPLICATION
This cables are used for interconnection of distribution boxes and end devices, where continued functionality is required during a fire situation. The cables are very suitable for various indoor and outdoor applications, including routing between buildings within ducts and inside building up to riser shafts.
Standards
Basic design to Telcordia GR409-CORE / TIA/EIA 568B.3 / ICEA-S-83-596
FIRE PERFORMANCE
Circuit Integrity |
IEC 60331-25; BS 6387 CWZ; DIN VDE 0472-814(FE180);
CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);
NF C32-070-2.3(CR1)
|
System circuit integrity |
DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
|
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;
CEI 20-37/2-1 ; BS 6425-1*
|
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;
CEI 20-37/2-2 ; BS 6425-2*
|
Minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
|
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
CABLE CONSTRUCTION
Optical fibers: Singlemode and multimode tight fibers, with tight buffer coating.
Fire Barrier: The tight buffered fibers are wrapped with fire blocking fiber glass yarns.
Inner Sheath(optional): Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 Ripcord(optional): An optional ripcord can be located under the outer sheath to facilitate jacket removal.
Armouring(optional):
STA: Corrugated steel tape armour
SWB: Steel wire braid
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -20°C - +60°C
Temperature range during installation (mobile state): 0°C - +50°C
Minimum bending radius: 10 times the outer diameter for unarmoured cables
20 times the outer diameter for armoured cables
Download details in PDF
Download details in Wore
|
|