Caledonian fireflix Cables
CABLE CONSTRUCTION
fireflix cables are constructed in the following typical design:
1. Solid/stranded annealed copper conductor
2. Glass mica tape/silicone rubber as flame barrier
3. XLPE/silicone rubber as insulation
4. LSZH/Flame retardant RPVC as sheath
fireflix cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be elastomeric (EPR, SR), thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.
INTERNATIONAL STANDARD
The fireflix cables manufactured by Caledonian comply with either one or combination of the following standards.
BS 6387
IEC 60331
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1
|
|
|
PRODUCTS
Fire Resistan NEK606 Water Blocked Offshore & Marine Cable
Water Blocked Fire Resistant Power and Control Cables
Water Blocked P5 or P5/P12 BFOU 0.6/1KV
Applications
These cables are fire resistant, flame retardant, low smoke,halogen free and mud resistant, used for control, power and lighting systems.
Standards
IEC 60092-353 IEC 60092-351
IEC 60092-359 IEC 60332-1
IEC 60332-3-22 IEC 60754-1,2
IEC 61034-1,2 NEK 606:2004
VG 95218 part 29
Construction
Conductors: Tinned annealed stranded compacted copper to IEC 60228 class 2.
Insulation: Mica tape + Halogen free EPR/Mica tape + XLPE.
Filler: Water blocking fillers, if required.
Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P5). Halogen free, mud resistant thermosetting compound, SHF MUD (for TYPE P5/P12), coloured black.
Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
Download details in PDF