Caledonian FIREGUARD Cables


CABLE CONSTRUCTION
FIREGUARD cables are constructed in the following typical design:
  1. Solid/stranded annealed copper conductor
   2. Glass mica tape/silicone rubber as flame barrier
  3. XLPE/PVC as insulation
  4. Normal or Flame retardant FRPVC as sheath
FIREGUARD cables are offered in either single core, multicore or multi-pair constructions.
The insulation material is usually PVC with different levels of fire retardance properties to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.

INTERNATIONAL STANDARD
The FIREGUARD cables manufactured by Caledonian comply with either one or combination of the following standards.
IEC 60332-1
IEC 60332-3C

 

 

PRODUCTS

Fire Retardant PVC Sheathed Cables (FIREGUARD)
Flame Retardant Instrumentation Cables
Flame Retardant Overall Screened Instrumentation Cables (Multicore)
APPLICATION
The PVC versions (Part 1 Type 1&2) are generally use for indoor installation and suitable for wet and
damp areas. Generally used within industrial process manufacturing plants for communication, data
and voice transmission signals and services.
STANDARDS
Basic design adapted to BS 5308 Part1 Type 1 & 2
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 and 5 .
Insulation: Extruded cross-linked XLPE compound.
Overall Screen: Aluminium/polyester tape with 0.5mm2 screen (7/0.3mm) tinned copper drain wire.
Inner Sheath(optional): PVC compound
Armouring(optional): Galvanised steel wire
Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance,
anti rodent and anti termite properties can be offered as option. Compliance to fire performance
standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the
PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE
Insulation Colour: See technical information
Outer sheath: Black or blue
Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5secs max.
Minimum bending radius: 8 x Overall Diameter (unarmoured cable)
10 x Overall Diameter (armoured cable)