Caledonian fireflix Cables


CABLE CONSTRUCTION
fireflix cables are constructed in the following typical design:
  1. Solid/stranded annealed copper conductor
   2. Glass mica tape/silicone rubber as flame barrier
  3. XLPE/silicone rubber as insulation
  4. LSZH/Flame retardant RPVC as sheath
fireflix cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be elastomeric (EPR, SR), thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.

INTERNATIONAL STANDARD
The fireflix cables manufactured by Caledonian comply with either one or combination of the following standards.
BS 6387
IEC 60331
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1

 

 

 

PRODUCTS

Fire Resistant Power & Control Cables
300/500V SR Insulated Control Cables (2-4 Cores)
FFX200 05SZ1-U (PH60) (CU/SR/LSZH 300/500V Class 1)
APPLICATION
The cables are designed, for use as control cable for emergency services and fire circuit control.
STANDARDS
Basic design adapted from BS 7629-1
FIRE PERFORMANCE

Circuit Integrity

IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);
BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)

Circuit Integrity with mechanical shock

EN 50200(PH60); CEI 20-36/4-0

Circuit Integrity with mechanical shock & water spray

EN 50200 annex E

System circuit integrity

DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;
VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;
CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;
CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
300/500 V
CABLE CONSTRUCTION
Conductors:
Plain annealed copper wire, solid according to IEC(EN) 60228 class 1.
Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation Colour
Without earth conductor
2 cores black - blue
3 cores black - blue - brown
4 cores black - blue - brown - black
With earth conductor
3 cores black - blue - yellow/green
4 cores black - blue - brown - yellow/green
Sheath Colour: Orange (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 6 x Overall Diameter
Electrical PROPERTIES

Dielectric test:

2000 V r.m.s. x 5’ (core/core)

Insulation resistance

≥300 MΩ x km (at 20°C)

Short circuit temperature

350°C

300/500V SR Insulated Control Cables (2-4 Cores)

Download details in PDF

Download details in Word

 