Caledonian fireflix Cables


CABLE CONSTRUCTION
fireflix cables are constructed in the following typical design:
  1. Solid/stranded annealed copper conductor
   2. Glass mica tape/silicone rubber as flame barrier
  3. XLPE/silicone rubber as insulation
  4. LSZH/Flame retardant RPVC as sheath
fireflix cables are offered in either single core, multicore or multi-pair constructions.
The insulation material can be elastomeric (EPR, SR), thermosetting (XLPE, LSZH) or thermoplastic (EVA, LSZH) to meet different stringent environment requirement. The cables may be armoured or braided, with or without metallic screen, depending on different applications.

INTERNATIONAL STANDARD
The fireflix cables manufactured by Caledonian comply with either one or combination of the following standards.
BS 6387
IEC 60331
IEC 60332-1
IEC 60332-3C
IEC 61034-1/2
IEC 60754-1

 

 

 

PRODUCTS

Fire Resistant Power & Control Cables
300/500V Mica+XLPE Insulated, LSZH Sheathed Power Cables (Single Core)
FFX300 05mRZ1-R (CU/MGT+XLPE/LSZH 300/500V Class 2)
APPLICATION
The cables are designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, lifts, escalators, and high-rise buildings.
STANDARDS
Basic design to IEC 60502-1
FIRE PERFORMANCE

Circuit Integrity

IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);
CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);
NF C32-070-2.3(CR1)

System circuit integrity

DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;
VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;
CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;
CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
300/500 V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Mica glass tape covered by extruded cross-linked XLPE compound
Earth Conductor(optional): Uninsulated solid or stranded tinned copper conductor.
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 8 x Overall Diameter
Electrical PROPERTIES

Dielectric test:

2000 V r.m.s. x 5’ (core/core)

Insulation resistance

1000 MΩ x km (at 20°C)

Short circuit temperature

250°C

Fire Resistant Power & Control Cables


Download details in PDF

Download details in Word


Caledonian Cables |FAQ |© 2020